Configure the gateway

This example connects a substation RTU over IEC 104 and makes its data available to two systems: an OPC UA client (a historian or MES) and a Modbus master (a PLC). Commands from the OPC UA side go back to the RTU.

┌─────── Gateway ───────┐ ──OPC UA──▶ Historian
RTU ───IEC 104────▶ │ client ─▶ 2 servers │
192.168.10.5:2404 └───────────────────────┘ ──Modbus──▶ Line PLC

You can build it in the gateway’s web UI, or in the desktop tester first and copy the configuration file over (see Move a configuration).

New endpoint, name RTU Substation A, protocol IEC 60870-5-104, role Client:

Setting Value
Host 192.168.10.5
Port 2404
Common address (ASDU) 1
General interrogation on connect on
Start automatically on

Save it and open the endpoint. Check that the values arrive before you go on.

2. The targets: an OPC UA server and a Modbus server

Section titled “2. The targets: an OPC UA server and a Modbus server”

OPC UA server (OPC UA for historian, protocol OPC UA, role Server):

Setting Value Notes
Port 4840
Folder ProtocolBridge the points appear below Objects/ProtocolBridge
Clients may write on writes become commands
Security None and secured
Allow anonymous users off add Users instead

Modbus server (Modbus for PLC, protocol Modbus TCP, role Server): Port 502, Unit id 0 (answers every unit id).

Open Mappings and add:

Source Source address Target Target address Target type Scale / offset Forward commands
RTU Substation A * OPC UA for historian (same) (same) 1 / 0 on
RTU Substation A 4001 Modbus for PLC HR:40001 Integer 10 / 0 off
RTU Substation A 1001 Modbus for PLC CO:1 (same) 1 / 0 off
  • The first mapping publishes every RTU point on OPC UA under its IEC 104 address, and sends OPC UA writes back to the RTU as IEC 104 commands. The RTU’s confirmation or rejection is returned to the OPC UA client.
  • The second turns the measured value at IOA 4001 (e.g. 49.97 Hz) into a whole number for the PLC: 49.97 × 10 = 499.7, rounded to 500 in holding register 40001.
  • The third exposes the breaker state at IOA 1001 as coil 1.

The Last value column shows what passes through each mapping.

Everything is saved in %ProgramData%\ProtocolBridge\gateway.json. The example above looks like this (driver settings that keep their defaults are left out):

gateway.json
{
"endpoints": [
{ "id": "rtu-a", "name": "RTU Substation A", "protocol": "iec104", "role": "Client",
"settings": { "host": "192.168.10.5", "port": "2404", "common_address": "1" } },
{ "id": "opcua", "name": "OPC UA for historian", "protocol": "opcua", "role": "Server",
"settings": { "port": "4840", "allow_anonymous": "false" } },
{ "id": "plc", "name": "Modbus for PLC", "protocol": "modbus", "role": "Server",
"settings": { "port": "502", "unit_id": "0" } }
],
"mappings": [
{ "id": "m1", "sourceEndpointId": "rtu-a", "sourceAddress": "*",
"targetEndpointId": "opcua", "forwardCommands": true },
{ "id": "m2", "sourceEndpointId": "rtu-a", "sourceAddress": "4001",
"targetEndpointId": "plc", "targetAddress": "HR:40001", "targetType": "Integer", "scale": 10 },
{ "id": "m3", "sourceEndpointId": "rtu-a", "sourceAddress": "1001",
"targetEndpointId": "plc", "targetAddress": "CO:1" }
],
"calculations": []
}

Settings are text, and their keys are the driver’s setting names. Missing fields take their defaults; unknown fields are ignored.

  1. Build and test the configuration in the desktop app.
  2. Copy %LOCALAPPDATA%\ProtocolBridge\desktop.json from the laptop to the gateway as %ProgramData%\ProtocolBridge\gateway.json.
  3. Change the addresses that differ on site (for example, server endpoints that listened on 127.0.0.1 during the test).
  4. Restart the service: Restart-Service ProtocolBridgeGateway.