Live data and commands
Open an endpoint from the Endpoints section of the explorer to see its live data on the Points tab. The page is the same for every protocol.
Connection health
Section titled “Connection health”Above the points of a client endpoint, four tiles show whether the data is fresh, without starting a trace:
| Tile | What it says |
|---|---|
| Connection | Online for 2 h 5 min, since when, and how many times the connection was lost since the endpoint started. While not online: the state (Connecting, Stopped) and why. |
| Last update | how long ago the device last delivered data, changed or not: a completed poll, or a received message. For a polling protocol also the poll interval and how long the last poll cycle took. More than three poll intervals without a poll is marked stale. |
| Points | how many points there are, how many are good and bad, and how many changed in the last 10 s. |
| Errors | while an error goes on (the same Modbus exception every poll, for example): Failing for 2 min, with its message and when it started. Otherwise how many errors began in the last 10 minutes and when the last one was. Show frames opens the Troubleshoot tab. |
Errors are exceptions, timeouts, negative confirmations, refused or unanswered commands and lost connections. An error that every poll repeats counts once, from the first poll that had it to the first poll without it, so a missing register does not fill the counter; a one-off failure counts each time it happens.
Every client protocol reports polls, updates and errors. What counts as an update depends on how the protocol gets its data:
| Protocol | Polls? | Last update advances on |
|---|---|---|
| Modbus TCP, Siemens S7, EtherNet/IP | yes | every poll |
| OPC XML-DA | yes, in both modes | every Read cycle, or every SubscriptionPolledRefresh answer |
| OPC DA | in Read mode | every read cycle (Read), every data change (Subscription) |
| IEC 104 | no | every received data message |
| DNP3 | no | every answer from the outstation, also an event poll without events |
| OPC UA | no | every publish response, also a keep-alive without changes |
| Simulator | no | every tick, changed values or not |
Only polling endpoints show a poll interval and cycle time, and only their values turn stale. Server endpoints have no health strip.
The points table
Section titled “The points table”| Column | Meaning |
|---|---|
| Address | the point’s address in the protocol’s own format |
| Name | the point’s description, if it has one (see Names below); a long name is cut, the whole name is its tooltip. A lock before it marks a read-only point |
| Type | Boolean, DoublePoint, Integer, Float, Counter or Bitstring |
| Value | the latest value; — for a defined point that has not been received yet |
| Quality | Good, or the quality bits such as IV (invalid) or NT (not topical); then the value’s flags as small labels (see Flags below). For a bad point also why, and when it was last good |
| Time | the device’s time stamp, or the time the value arrived |
| Age | how fresh the value is (client endpoints, see below) |
| Trend | the recent history of the value |
Age: is the value fresh?
Section titled “Age: is the value fresh?”Age measures freshness, not activity. For a polled point (Modbus, S7, XML-DA, OPC DA in Read
mode) it is the time since the last
poll that read the value, changed or not: a register that has held 21.5 for an hour but is
read every second has an age under a second. For a point the device sends by itself (an IEC 104
spontaneous value, a DNP3 event, an OPC UA data change) it is the time since the value’s time stamp. The column header’s tooltip says
which applies.
When the device stops answering, the ages of a polled endpoint keep growing, and after three poll intervals they read stale, in words as well as in colour. That is how a frozen value is told apart from a value that just does not change.
Why a point is bad
Section titled “Why a point is bad”Under a bad point’s quality the table shows the reason in the device’s terms, for example Modbus exception: Illegal data address for a register the device does not have, object does not exist for a missing S7 data block, BadNodeIdUnknown for an OPC UA variable the server does not know, Bad: Comm Failure for an OPC DA item or Flags from the outstation: COMM_LOST for a DNP3 point, and when the point was last good: last good 12:38:02 (1 min ago), or no good value since the endpoint started.
Some devices say more about a value than good or bad. These facts are shown as small labels next to the quality; hover over a label for its meaning. A value with flags but no quality bits is still good: mappings, calculations, the health tiles and Age treat it like any good value.
| Flag | Meaning |
|---|---|
| test | the value comes from a device in test mode |
| failure | the device reports an internal failure for this value |
| oscillatory | the value oscillates; the device suppresses changes |
| inconsistent | the device found the value inconsistent |
| inaccurate | the value is inaccurate |
| out of range | outside the value’s configured range |
| bad reference | the device’s reference (calibration) is bad |
| clock not synchronized | the time stamp comes from an unsynchronised clock |
| clock failure | the device’s clock has failed |
| polled | read by polling because the device’s preferred delivery (reports) is not available |
| device faulted | the device reports a major fault; values may not be updated by its program |
Today IEC 61850 sets them (see IEC 61850), and EtherNet/IP sets device faulted (see EtherNet/IP). Server endpoints do not send flags on; a mapping keeps them in the gateway and in central.
Give a point a name when you add it (the Name field of Add point), in a CSV file (the
name column, see Import and export points), or take the name the
device proposes in Detect points. In Multiple points, {n} in the name numbers the
points: with an address pattern it is the number in the address (start index and padding
included), otherwise 1, 2, 3, … So Pump {n} speed gives Pump 1 speed, Pump 2 speed, … Names
have up to 255 characters; shorter ones read better in tables.
Read-only points
Section titled “Read-only points”A point can be marked read-only when the device accepts no writes to it: a Logix tag whose External Access is Read Only, an OPC UA variable without write access, an IEC 61850 status or measurement. The table shows a lock before its name, and a client endpoint offers no command for it. If a command reaches it anyway (from the API, a mapping or central), it is answered Rejected with The point is read-only; the command was not sent., nothing goes to the device, and the endpoint’s health counts it like a refusal from the device.
Where the mark comes from:
- Detect points proposes it from what the device says (EtherNet/IP External Access, IEC 61850
[ST]and[MX]). A point you already have keeps its own mark; tick Use the device’s access to take the device’s, which lists each change first. Protocols that do not say (Modbus, IEC 104, DNP3, S7) never change it. - An OPC UA or OPC XML-DA client that browses marks the variables the server reports as not writable when they become points.
- You set or clear it yourself: the Read-only box of Add point (for Multiple points,
all of them), the Read-only column of the table, or the
readOnlycolumn of a CSV file (see Import and export points).
Changing the mark takes effect at once, without reconnecting. The Mappings page warns about a mapping that forwards commands to a read-only point: those commands are refused.
On a server endpoint the mark protects the point from the peer: a write that SCADA sends to a read-only point is refused with the protocol’s own answer (a Modbus exception, an IEC 104 negative confirmation, a DNP3 refusal, OPC UA BadNotWritable) and is not forwarded by any mapping. An OPC UA server endpoint also shows the variable as not writable.
Find points
Section titled “Find points”The filter row right above the points narrows the table. Type in the Find box to find points
by address, name, description or type in a long list. The Show list (All, Bad quality,
Changed < 10 s, Read-only, each with its count) keeps the points that need attention, the
ones that are moving, or the read-only ones. Column filters adds a filter under each header;
the Quality filter also finds flags (test). Refresh all on the toolbar asks the device for
all its values again (for IEC 104 this is a general interrogation). Stop and Start on the
toolbar disconnect and reconnect the endpoint.
Send a command (client endpoints)
Section titled “Send a command (client endpoints)”- Click command at the end of a point’s row: the command form opens under the row. For an address that is not in the table, choose Command to another address in the ⋯ menu at the end of the button row above the table, and type the address.
- Pick the Type and enter the Value;
BooleanandDoublePointhave ON and OFF. - Tick Select before operate if the device expects a select first. The option appears only for IEC 104 and DNP3, the protocols that have it (not for IEC 104 bitstring commands); other protocols write directly. IEC 61850 follows the control model of the object instead (see IEC 61850).
- Click Send.
A read-only point has no command link (see Read-only points).
The result comes back from the device: Confirmed, Rejected, Timeout or Not connected. That tells you not only that the command was sent, but whether the device accepted it. To see the frames of a command, start the frame trace on the Troubleshoot tab first: the result then offers Show frames, which opens the trace with only that command’s frames (the same for Refresh). See Troubleshoot a connection.
Examples:
- IEC 104: a single command to IOA
2001. - Modbus: write coil
CO:1or holding registerHR:40101. - DNP3: a control to
BO:0or an analog output toAO:0. - S7: write
DB1.DBW10:INT.
Publish a value (server endpoints)
Section titled “Publish a value (server endpoints)”On a server endpoint the same form publishes a value instead of sending a command. Use it to play the
device’s part towards a SCADA system under test: publish 1 on an alarm point and check that
SCADA raises the alarm, or set a measured value out of range.
Click publish at the end of a point’s row (or choose Publish to another address in the ⋯ menu above the table for an address that is not in it), enter the value and click Publish. Tick Invalid quality to check how SCADA shows a failed measurement. Commands that SCADA sends to the server show up as new values; with a mapping that has forward commands on, they are sent on to the real device. Commands to a read-only point of the server are refused.
Replay a recorded or simulated source
Section titled “Replay a recorded or simulated source”Map any client endpoint onto a server endpoint (see Concepts). A Simulator client gives changing values, and a mapping with a target type, scale and offset shapes them into what the SCADA system expects.