Connect an IEC 61850 IED
Protocol Bridge connects to IEC 61850 IEDs (protection relays, bay controllers, meters) as an MMS client (IEC 61850-8-1, Edition 2, and Edition 1 where it behaves the same). It reads their data objects with the IED’s own quality and time stamps, takes changes from the IED’s reports, operates controllable objects with the IED’s control model, and can detect the points of an IED by browsing its model.
Add an endpoint with the protocol IEC 61850 (MMS) and the role Client. One endpoint is one IED; a station gets one endpoint per IED.
Connection
Section titled “Connection”| Setting | Example | Notes |
|---|---|---|
| Host | 192.168.10.21 |
the IED |
| Port | 102 |
|
| Password | only for IEDs with ACSE password authentication | |
| Remote TSEL / SSEL / PSEL | 0001 / 0001 / 00000001 |
the defaults of nearly every IED |
| Remote AP title / AE qualifier | 1.1.1.999.1 / 12 |
empty unless the IED asks for them |
If the IED is configured otherwise, its SCL file (CID or SCD) has the values under
ConnectedAP/Address: OSI-TSEL, OSI-SSEL, OSI-PSEL, OSI-AP-Title,
OSI-AE-Qualifier. Some IEDs accept only clients they know: then set Local AP title and
Local AE qualifier as listed in the IED’s configuration.
Points
Section titled “Points”A point is an object reference with its functional constraint, written as the IED’s engineering tool shows it:
| Point | What it reads |
|---|---|
IED1CTRL/XCBR1.Pos[ST] |
breaker position (stVal, a double point) with its quality and time |
IED1LD0/MMXU1.TotW[MX] |
total active power (mag.f) |
IED1LD0/MMXU1.PhV.phsA[MX] |
phase A voltage |
IED1LD0/MMTR1.TotWh[ST] |
energy counter (actVal) |
IED1PROT/PTOC1.Op[ST] |
protection operate (general) |
IED1CTRL/XCBR1.Pos[CO] |
the breaker as a controllable object: shows its position, takes commands |
IED1LD0/GGIO1.SetPt.setMag.f[SP] |
an attribute named in full |
A point that names a data object reads its value attribute (stVal, mag.f, actVal,
general, setMag.f, …). For other data objects, name the attribute. Names are
case-sensitive, as in the IED.
| IEC 61850 | Point type |
|---|---|
| BOOLEAN | Boolean |
| Dbpos | DoublePoint (0 intermediate, 1 off, 2 on, 3 bad) |
| integers, enumerations | Integer (actVal: Counter) |
| FLOAT32, FLOAT64 | Float |
Quality, time stamps and flags
Section titled “Quality, time stamps and flags”The IED’s quality becomes the usual quality bits: invalid → IV; questionable and old data → NT; overflow → OV; substituted → SB; operator blocked → BL, and these are named in the point’s reason. The IED’s other details become flags next to the quality: test, failure, oscillatory, inconsistent, inaccurate, out of range and bad reference. A value in test mode therefore stays good, which is what you want during commissioning, and its test label says where it comes from.
The time stamp is the IED’s own. When the IED says its clock is not synchronised or has failed, the value carries clock not synchronized or clock failure.
A point the IED does not have stays invalid with the reason, for example the IED’s XCBR1 has no ‘Pos2’; the other points are read.
Reports or polling
Section titled “Reports or polling”In the default mode, Reports, Protocol Bridge uses the IED’s report control blocks: it enables
every block whose data set holds one of the points (or the blocks you list in Report control
blocks, e.g. IED1LD0/LLN0.brcbMX01[BR]) and asks for all their values once. After that the
IED sends changes as they happen. Points that no report covers are polled every Poll
interval.
- Buffered blocks (
[BR]) keep the events while the connection is down; after a reconnect Protocol Bridge continues where it stopped, so no event is lost and none is repeated. - A block that another client (often the station SCADA) already uses is left alone: its points are polled, and the endpoint’s health names the block. Every point that is polled in this mode (its block is in use, or no block holds it) carries the polled flag. With When an RCB cannot be used set to Fail, the endpoint does not go online instead, for sites where reports are required.
- Integrity period asks the IED to repeat all values of a block that often.
The mode Poll reads every point each poll interval and uses no report control blocks.
Commands
Section titled “Commands”Send a command to a [CO] point. Protocol Bridge runs the object’s control model as the IED has it
configured (ctlModel):
| Control model | What happens |
|---|---|
| direct, normal security | the IED operates at once |
| select before operate, normal security | Protocol Bridge selects the object, then operates |
| direct, enhanced security | Protocol Bridge operates and waits until the IED reports the end of the operation |
| select before operate, enhanced security | select, operate, and wait for the end |
| status only | the command is refused |
For a double point (a breaker, a disconnector) send 2 to close (on) and 1 to open (off). If
the IED refuses, the command fails with the IED’s own reason, for example blocked by
interlocking, object already selected or blocked by switching hierarchy (the IED is in
local mode). Originator category (default RemoteControl) and Originator identification
are sent with each command; Interlock check and Synchro check ask the IED to check before
operating.
Commands to settings ([SP], [SE], [CF], …) write the value. Status ([ST]) and
measurements ([MX]) are read-only; command the [CO] point instead.
Detect points
Section titled “Detect points”You do not need the IED’s point list: Detect points on the endpoint’s page browses the
IED’s model and proposes one point per data object: status and measurements, and on request the
controllable objects ([CO]) and the settings and configuration. Pick the ones you want and add
them. With Detect points on connect the endpoint adds the status and measurement points by
itself each time it connects.
Each proposed point gets the IED’s own description of the data object (dU, or d), for
example Feeder 3 active power, as its description; its address is its name. You can change the
description before adding the point. A point you already have keeps its description; tick
Use the device’s descriptions to take the IED’s for those too: the preview lists each
change first.
Status and measurements ([ST], [MX]) are proposed as
read-only points, so no command is sent to them;
controls and settings are writable. A point you already have keeps its mark unless you tick
Use the device’s access.
When it does not connect
Section titled “When it does not connect”Test connection (or the Troubleshoot tab) walks through the steps and stops at the first one that fails, with what to change:
| Step | Typical failure | What to check |
|---|---|---|
| Transport connection | the IED refuses the transport selector | Remote TSEL |
| Association | session or presentation selector unknown; AP title not recognised; password required or wrong; the IED closes the connection without an answer | Remote SSEL, Remote PSEL, Remote AP title, Password, the IED’s list of allowed clients |
| MMS initiate | the IED refuses the PDU size | Max PDU size (try 32000) |
| Identification | the IED does not support Identify | nothing: it is not needed |
| Logical devices | no logical devices | the IED’s configuration (CID file) |
| Configured points | a reference the IED does not have | the object reference, or detect the points |
The frame trace shows every message with its meaning: reads with object references and values, reports with the members of their data sets, the steps of each command and the IED’s reasons.
No IED at hand?
Section titled “No IED at hand?”Protocol Bridge has no IEC 61850 server endpoint, so use an IEC 61850 server simulator. The example
servers of the open-source libiec61850 work
well: server_example_basic_io has measurements, status points, report control blocks and
controllable objects, and server_example_control has an object for every control model. Start
one with a port, for example server_example_basic_io 10102, connect an endpoint to host
127.0.0.1 and that port, and detect its points, or use
simpleIOGenericIO/GGIO1.AnIn1[MX] and simpleIOGenericIO/GGIO1.SPCSO1[CO].