Connect an Allen-Bradley Logix controller (EtherNet/IP)

Protocol Bridge talks to Allen-Bradley ControlLogix, CompactLogix and GuardLogix controllers directly over EtherNet/IP (CIP explicit messaging). It reads and writes tags by their names, as Studio 5000 shows them, finds the tags by browsing the controller, and reads attributes of other CIP devices such as drives, I/O adapters and power monitors.

No Rockwell data server (RSLinx, FactoryTalk Linx) is needed, nothing is installed on the computer, and nothing has to be enabled on the controller. Protocol Bridge uses unconnected messages only: it opens no CIP connection in the controller and does not change its I/O configuration.

Add an endpoint with the protocol EtherNet/IP (Allen-Bradley Logix) and the role Client. One endpoint is one controller; a chassis with three controllers gets three endpoints.

Setting Example Notes
Host 192.168.1.20 the Ethernet module (1756-EN2T, EN2TR, EN4TR, …) or the controller’s built-in port
Port 44818
Family Logix Generic CIP for drives, adapters and other CIP devices
Route path 1,0 see below
Poll interval 1000 ms every point is read each interval
Requests in flight 1 up to 4; the controller shares its message buffers with every HMI and client
Read controller state every 5000 ms for the Controller.* points and the device faulted flag

Route path says how to get from the Ethernet port to the controller, as pairs of port, link, the way Rockwell writes it:

Route path Meaning
1,0 backplane, slot 0. Also CompactLogix with a built-in Ethernet port
1,3 backplane, slot 3 (the controller sits in slot 3)
1,2,2,192.168.2.10,1,0 backplane slot 2 (a second Ethernet module), out of its port 2 to 192.168.2.10, then that chassis’ backplane, slot 0
(empty) the device the host points at, for generic CIP devices

Tags are written as in Studio 5000; upper or lower case does not matter:

Point What it reads
Line1_Speed a controller-scope tag
Program:MainProgram.Count a program-scope tag
Motors[3].Current a member of an element of a UDT array
Grid[2,4] an element of a two-dimensional array (up to three dimensions)
Status.7 bit 7 of an integer tag
Flags[37] one BOOL of a BOOL array
T1.ACC, T1.DN members of a TIMER (also COUNTER, CONTROL and AOI members)
Line1_Speed:REAL with the type it must have (optional)

Protocol Bridge takes the type from the controller. If you add a type after a colon and the controller’s tag has another type, the point turns invalid and says both types: useful after a program change, so a retyped tag does not silently give wrong numbers.

Attributes of other CIP devices are written @class/instance/attribute:TYPE, with the type required: @0x01/1/5:WORD is the Identity object’s status, @0x0F/3/1:REAL a Parameter object. Endpoints of the family Generic CIP accept only this form.

Controller points come from the controller’s Identity object: Controller.Status (the status word), Controller.Faulted (a major fault), Controller.MinorFault, and for Logix Controller.Run, Controller.Mode (6 Run, 7 Program) and Controller.Keyswitch (1 Run, 2 Program, 3 Remote). They are read-only.

Logix type Point type
BOOL, bits, BOOL array elements, .DN-style bits Boolean
SINT, INT, DINT, LINT, USINT, UINT, UDINT, ULINT Integer (LINT and ULINT exact above 2^53)
REAL, LREAL Float
BYTE, WORD, DWORD, LWORD (CIP attributes) Bitstring

STRING tags are not numbers and cannot be points.

Every point is read each poll interval. Protocol Bridge packs the reads into as few requests as the controller allows (about 500 bytes each): array elements close together are read as one range, and when several points are members of the same element of a UDT (Motors[3].Current, Motors[3].Speed, …), the element is read once if that is shorter. Long tag names cost space in every request, so short names fit more points into one request.

EtherNet/IP carries no quality and no time stamp: a point is good when it is read, with the time it arrived. A tag that fails turns only its own point invalid, with the reason in words, for example path segment error (tag or object not found). A REAL that reads as NaN or infinity is invalid. When the connection is lost, every point turns invalid.

While the controller reports a major fault, its program does not run. Protocol Bridge still reads the values, and every point carries the flag device faulted.

A command writes the tag with its type from the controller. Single bits (Status.7, Flags[37]) are changed with a read-modify-write in the controller, so the other bits of the word are not touched. Numbers are rounded to whole numbers for integer tags and refused before anything is sent when they do not fit the type. Generic attributes are set with Set_Attribute_Single.

A refused write says why: the tag does not exist, its External Access is Read Only or None, it is a constant or a safety tag, or the type does not match. There is no select-before-operate; writes take effect at once.

Detect points on the endpoint’s page lists the controller’s tags and proposes one point per value: every atomic tag, every member of a structure or AOI and every array element. The tag’s name is the point’s name, so no other name is proposed. Options:

  • Controller scope only: leave out the programs’ tags.
  • Include module-defined I/O tags (Local:1:I.Data, …): off by default.
  • Include status bits of timers, counters and controls (.EN, .TT, .DN): on by default.
  • Elements offered per array: 64 by default. Longer arrays offer their first elements, with a note on how many were left out.

System tags, STRING tags and tags with External Access None are left out; tags with External Access Read Only are offered as read-only points: Protocol Bridge sends no write to them. Detection stops at 20,000 points. With Detect points on connect the endpoint adds the controller’s points by itself each time it connects.

Tag descriptions cannot be read from the controller. Export the tags from Studio 5000 and import their descriptions with the description column of a point CSV.

Test connection (or the Troubleshoot tab) walks through the steps and stops at the first one that fails, with what to change:

Step Typical failure What to check
List Identity the device does not answer, or answers with something else host and port; the device speaks EtherNet/IP
RegisterSession the session is refused CIP Security enforced on the module (not supported), or no free sessions
Route to target port not available, link address not valid, invalid segment in path Route path: the controller’s slot
Target identity not a Logix controller; a Micro800 Route path, or Family Generic CIP; Micro800 controllers are not supported
Configured points a tag that does not exist, an index beyond the end of an array, External Access the tag name and its program, the array size, the tag’s External Access

A busy controller (resource unavailable, unconnected request timed out) shares its message buffers with every HMI and client: lower Requests in flight or raise Poll interval. The frame trace shows every message with its meaning: the route path, the packed requests with their tag names and the values read and written.

Micro800 controllers, SLC 500, MicroLogix and PLC-5 (PCCC), CIP Security, I/O connections and produced/consumed tags. Protocol Bridge cannot act as a target that a controller’s MSG instruction reads.

The Protocol Bridge source has a test controller with tags of every type, arrays, UDTs, a TIMER and two programs: cargo run -p enip --example enip_server_sim -- 127.0.0.1:44818. Connect an endpoint to host 127.0.0.1 with route path 1,0 and detect its points, or use DintTag, Motors[1].Current and Program:MainProgram.Count.


EtherNet/IP and CIP are trademarks of ODVA, Inc.; Allen-Bradley, Logix, ControlLogix, CompactLogix and GuardLogix are trademarks of Rockwell Automation, Inc. Protocol Bridge is not affiliated with or endorsed by either.