Finding the byte order
Modbus only knows 16-bit registers. A 32-bit or 64-bit value spans two or four of them, and every manufacturer picks its own order. A wrong order still gives a number, just a wrong one, and manuals often get it wrong or leave it out. The register map may also start a value at an odd or at an even register.
The register explorer takes the guessing out: it reads a range of registers once and shows every possible start address with the value decoded in all four orders, side by side. You pick the cell that matches the device, and Protocol Bridge turns it into a point. Protocol Bridge never picks an order by itself: a wrong guess would look just as plausible as the right one.
The four byte orders
Section titled “The four byte orders”For a 32-bit value with bytes A B C D (A the most significant):
| Order | First register | Second register | Also called |
|---|---|---|---|
ABCD |
A B | C D | big-endian, the Modbus convention (the default) |
CDAB |
C D | A B | word swap, low word first |
BADC |
B A | D C | byte swap |
DCBA |
D C | B A | little-endian |
64-bit values (u64, i64, f64) follow the same rule over four registers; CDAB then means the
four words in reverse order. 16-bit values only change with BADC and DCBA (bytes swapped).
The endpoint setting Byte order of multi-register values applies to every point. A point that
differs gets its own order after the type: HR:40011:f32:CDAB.
Read registers
Section titled “Read registers”Open a Modbus TCP client endpoint and switch to Troubleshoot: the Registers panel is there. In the endpoint editor, Read registers opens the same panel for the settings you are editing, before you save them.
- Choose Holding registers or Input registers, enter the First register (
40001, or an address such asHR:40001) and the Count (up to 1000), and click Read. - Choose the Type. Changing it decodes the same registers again, without reading.
- Each row is a start register; the columns are the value in
ABCD,CDAB,BADCandDCBA.
Here the meter stores its values low word first. The value 50.0 shows up in the CDAB column at
HR:40001, while ABCD at HR:40001 shows a tiny number such as 2.3777e-41. (ABCD at HR:40002
also shows 50, because it reads the same two registers the other way round, from one register
later.)
Help to decide
Section titled “Help to decide”- Known value: type a value you can see on the device (its display, the vendor’s tool, an
example in the manual). Every matching cell is highlighted and listed above the table as an
address with type and order, for example
HR:40001:f32:CDAB. Floats match within 0.1 % unless you set a Tolerance (0.5, or1%); integers match exactly. - Dimmed values (with a
·) are floats that look implausible: not a number, infinite, a denormal (tiny) number, or larger than 1012 or smaller than 10-12. Hover for the reason. This is a hint only: nothing is hidden or chosen for you. - Start at shows only the rows that start at the first or the second register of the range (for 64-bit types, the first to fourth), for register maps where values start at odd or at even numbers. The registers are not read again.
- Auto-read reads again every 1, 2, 5 or 10 seconds and highlights the cells that changed. A counter that climbs by one in one column and jumps around in the others gives the order away. Auto-read stops when you close the panel, or after 10 minutes.
- Registers as shows the raw registers in hex, in decimal or as bits. Bits are for status
and alarm words: each register is shown as 16 bits, bit 15 on the left and bit 0 on the right
(hover a bit for its number, such as
HR:40001 bit 3). With auto-read, a bit that flipped since the previous read is marked, so you can toggle something on the device and see which bit moves.
A request that fails, for example because the range has a hole (exception 02, illegal data address), is listed with its range and a hint. The other requests are still shown; registers that could not be read stay empty, never 0.
Turn a cell into a point
Section titled “Turn a cell into a point”In the editor, hover a value: add puts the address into Points to poll (without the order
when it is the endpoint’s order, so HR:40001:f32 rather than HR:40001:f32:ABCD), and use
CDAB makes it the endpoint’s byte order. When you change the order, a note lists the configured
points without an order of their own whose values will change. Nothing is saved until you click
Save.
Which connection is used
Section titled “Which connection is used”Many Modbus devices accept only one or two connections at a time. So the explorer uses the endpoint’s own connection while it is online: its requests go out one at a time between the polls, and a poll that is due goes first. Polling continues and no second connection is opened. When the endpoint is connecting or faulted, its reconnect attempts pause while the explorer reads on a connection of its own; when it is stopped (or not saved yet), the explorer opens a connection just for the read.
The explorer only reads (function codes 3 and 4) and never writes. While the endpoint’s frame trace runs, Show frames filters the trace to the explorer’s requests and answers.