Connect to a device
Every device is a client endpoint. Click New endpoint on the toolbar (or + next to Endpoints in the explorer), choose the protocol and the role Client, and fill in the settings below. The form only shows the settings of the chosen protocol, each with its default value.
Modbus TCP energy meter
Section titled “Modbus TCP energy meter”| Setting | Example | Notes |
|---|---|---|
| Host | 192.168.1.50 |
the meter or the Modbus TCP gateway |
| Port | 502 |
|
| Unit id | 1 |
|
| Points to poll | HR:40001:f32, HR:40003, IR:30001:u32, CO:1, DI:10001 |
separated by commas |
| Poll interval (ms) | 1000 |
|
| Byte order of multi-register values | ABCD |
CDAB, BADC or DCBA if 32- and 64-bit values look wrong |
Address prefixes: HR holding register, IR input register, CO coil, DI discrete input.
The optional suffix sets the register type: u16 (default), i16, u32, i32, f32, and the
64-bit u64, i64, f64 (energy counters, doubles). A second suffix sets the byte order of one
point when it differs from the endpoint’s: HR:40011:f32:CDAB.
Not sure where a value starts or which byte order the meter uses? Read registers in the editor shows the registers in all four orders side by side: see Finding the byte order.
Protocol Bridge merges neighbouring addresses into one read request (Max gap to merge reads, Registers per read request), so a long point list stays fast.
Siemens S7 PLC
Section titled “Siemens S7 PLC”Works with S7-300, S7-400, S7-1200 and S7-1500. On S7-1200/1500, allow PUT/GET communication in the CPU properties and switch off optimized block access for the data blocks you read.
| Setting | Example | Notes |
|---|---|---|
| Host | 192.168.0.10 |
the CPU or its communication processor |
| Port | 102 |
|
| Rack / Slot | 0 / 1 |
S7-300: slot 2 |
| Addresses to poll | DB1.DBD0:REAL, DB1.DBD4:DINT, DB1.DBX8.0, DB1.DBW10:INT |
|
| Poll interval (ms) | 1000 |
Besides the polled addresses, the point CPU.Run shows the CPU state.
OPC UA server
Section titled “OPC UA server”| Setting | Example | Notes |
|---|---|---|
| Endpoint URL | opc.tcp://192.168.0.20:4840 |
|
| Security policy / mode | Basic256Sha256 / SignAndEncrypt |
None for a quick test |
| User name / Password | empty: anonymous | |
| Browse for variables | on | finds the server’s variables by itself |
| Nodes | ns=2;s=Pump1.Speed |
extra node ids to subscribe to |
With Browse for variables on, you do not have to type addresses: Protocol Bridge browses the
server from Browse root (i=85, the Objects folder) and subscribes to what it finds.
With a secured policy, the server has to trust Protocol Bridge and Protocol Bridge has to trust the server. The first connection is usually rejected; open Certificates, find the server’s certificate under Rejected and click Trust. Give the server the Protocol Bridge certificate shown under This application.
IEC 61850 IED
Section titled “IEC 61850 IED”| Setting | Example | Notes |
|---|---|---|
| Host | 192.168.10.21 |
the protection relay, bay controller or meter |
| Port | 102 |
|
| Points to read | IED1LD0/MMXU1.TotW[MX], IED1CTRL/XCBR1.Pos[CO] |
or use Detect points |
| Mode | Reports |
values from the IED’s reports; Poll to read every point each interval |
Reports, commands, point detection and the connection settings are explained in Connect an IEC 61850 IED.
DNP3 outstation (RTU, IED)
Section titled “DNP3 outstation (RTU, IED)”| Setting | Example | Notes |
|---|---|---|
| Host | 192.168.1.30 |
the RTU, IED or DNP3 gateway |
| Port | 20000 |
|
| Master link address / Outstation link address | 1 / 1024 |
as configured in the outstation |
| Enable unsolicited reporting | on | the outstation sends class 1, 2 and 3 events by itself |
| Class 1 / 2 / 3 event poll interval (ms) | 1000 / 10000 / 60000 |
0: disabled |
| Integrity poll interval (s) | 3600 |
reads every value again (class 0); 0: only after connecting and after an event buffer overflow |
After connecting, Protocol Bridge runs an integrity poll and then takes events as the outstation
reports them. Each event class can also be polled on its own interval, for example class 1
(often breaker and alarm states) every second and class 3 every minute. Classes that are due at
the same time are read in one request. The polls run whether unsolicited reporting is on or off,
so they also catch events of an outstation that reports unsolicited only for some classes. With
all three intervals at 0 and unsolicited reporting off, events are read when the outstation
says it has some.
Protocol Bridge confirms every unsolicited response, so the outstation removes those events from its buffer.
Allen-Bradley Logix controller (EtherNet/IP)
Section titled “Allen-Bradley Logix controller (EtherNet/IP)”| Setting | Example | Notes |
|---|---|---|
| Host | 192.168.1.20 |
the Ethernet module or the controller’s built-in port |
| Port | 44818 |
|
| Route path | 1,0 |
backplane, slot of the controller; CompactLogix: 1,0 |
| Points to read | Line1_Speed, Motors[3].Current, Program:MainProgram.Count |
or use Detect points |
Route paths, tag addresses, writing and point detection are explained in Connect an Allen-Bradley Logix controller.
No device at hand?
Section titled “No device at hand?”Use a Protocol Bridge server endpoint fed by the simulator as the device, as in the quick start: IEC 104, Modbus TCP, DNP3 and OPC UA have a server role. For IEC 61850, see No IED at hand?; for EtherNet/IP, see No controller at hand?.