Connect to a device

Every device is a client endpoint. Click New endpoint on the toolbar (or + next to Endpoints in the explorer), choose the protocol and the role Client, and fill in the settings below. The form only shows the settings of the chosen protocol, each with its default value.

Setting Example Notes
Host 192.168.1.50 the meter or the Modbus TCP gateway
Port 502
Unit id 1
Points to poll HR:40001:f32, HR:40003, IR:30001:u32, CO:1, DI:10001 separated by commas
Poll interval (ms) 1000
Byte order of multi-register values ABCD CDAB, BADC or DCBA if 32- and 64-bit values look wrong

Address prefixes: HR holding register, IR input register, CO coil, DI discrete input. The optional suffix sets the register type: u16 (default), i16, u32, i32, f32, and the 64-bit u64, i64, f64 (energy counters, doubles). A second suffix sets the byte order of one point when it differs from the endpoint’s: HR:40011:f32:CDAB.

Not sure where a value starts or which byte order the meter uses? Read registers in the editor shows the registers in all four orders side by side: see Finding the byte order.

Protocol Bridge merges neighbouring addresses into one read request (Max gap to merge reads, Registers per read request), so a long point list stays fast.

Works with S7-300, S7-400, S7-1200 and S7-1500. On S7-1200/1500, allow PUT/GET communication in the CPU properties and switch off optimized block access for the data blocks you read.

Setting Example Notes
Host 192.168.0.10 the CPU or its communication processor
Port 102
Rack / Slot 0 / 1 S7-300: slot 2
Addresses to poll DB1.DBD0:REAL, DB1.DBD4:DINT, DB1.DBX8.0, DB1.DBW10:INT
Poll interval (ms) 1000

Besides the polled addresses, the point CPU.Run shows the CPU state.

Setting Example Notes
Endpoint URL opc.tcp://192.168.0.20:4840
Security policy / mode Basic256Sha256 / SignAndEncrypt None for a quick test
User name / Password empty: anonymous
Browse for variables on finds the server’s variables by itself
Nodes ns=2;s=Pump1.Speed extra node ids to subscribe to

With Browse for variables on, you do not have to type addresses: Protocol Bridge browses the server from Browse root (i=85, the Objects folder) and subscribes to what it finds.

With a secured policy, the server has to trust Protocol Bridge and Protocol Bridge has to trust the server. The first connection is usually rejected; open Certificates, find the server’s certificate under Rejected and click Trust. Give the server the Protocol Bridge certificate shown under This application.

Setting Example Notes
Host 192.168.10.21 the protection relay, bay controller or meter
Port 102
Points to read IED1LD0/MMXU1.TotW[MX], IED1CTRL/XCBR1.Pos[CO] or use Detect points
Mode Reports values from the IED’s reports; Poll to read every point each interval

Reports, commands, point detection and the connection settings are explained in Connect an IEC 61850 IED.

Setting Example Notes
Host 192.168.1.30 the RTU, IED or DNP3 gateway
Port 20000
Master link address / Outstation link address 1 / 1024 as configured in the outstation
Enable unsolicited reporting on the outstation sends class 1, 2 and 3 events by itself
Class 1 / 2 / 3 event poll interval (ms) 1000 / 10000 / 60000 0: disabled
Integrity poll interval (s) 3600 reads every value again (class 0); 0: only after connecting and after an event buffer overflow

After connecting, Protocol Bridge runs an integrity poll and then takes events as the outstation reports them. Each event class can also be polled on its own interval, for example class 1 (often breaker and alarm states) every second and class 3 every minute. Classes that are due at the same time are read in one request. The polls run whether unsolicited reporting is on or off, so they also catch events of an outstation that reports unsolicited only for some classes. With all three intervals at 0 and unsolicited reporting off, events are read when the outstation says it has some.

Protocol Bridge confirms every unsolicited response, so the outstation removes those events from its buffer.

Allen-Bradley Logix controller (EtherNet/IP)

Section titled “Allen-Bradley Logix controller (EtherNet/IP)”
Setting Example Notes
Host 192.168.1.20 the Ethernet module or the controller’s built-in port
Port 44818
Route path 1,0 backplane, slot of the controller; CompactLogix: 1,0
Points to read Line1_Speed, Motors[3].Current, Program:MainProgram.Count or use Detect points

Route paths, tag addresses, writing and point detection are explained in Connect an Allen-Bradley Logix controller.

Use a Protocol Bridge server endpoint fed by the simulator as the device, as in the quick start: IEC 104, Modbus TCP, DNP3 and OPC UA have a server role. For IEC 61850, see No IED at hand?; for EtherNet/IP, see No controller at hand?.